Installation Instructions for Innotech Genesis Systems
Edition 011100
2-9
Figure 2-9. DIN Rail Dimensions.
2-3.2. INSTALLATION GUIDELINES. To ensure continued reliable operation of
the Genesis II System, the following installation guidelines should be observed:
The Genesis II Digital Controller should be installed in a position that provides easy
access to the front panel and sufficient room for power, and input/output cabling. Also,
the Digital Controller should be mounted such that the controls are in easy reach of the
user.
Install LEMs as close as possible to the Digital Controller and side-by-side on the DIN
rail. Refer to Paragraph 2-3 and Figure 2-8.
Placement of the Genesis II Digital Controller should take into account the optimum
viewing angle of the Liquid Crystal Display (LCD), which is approximately 45
o
vertically
and 90
o
horizontally (see Figure 2-10).
Do not mount any unit of the system near high voltage, high current cables or sources of
strong radio frequency emissions such as transmitter antenna cables.
The ambient temperature of the Digital Controller and LEMs at the installation site should
not exceed the 0-40ºC temperature range. Ideally, the installation site should have a stable
ambient temperature close to 20
o
C.
Mount the units in an area with minimum vibration and minimum exposure to mechanical
damage.
Figure 2-10. Digital Controller Display, Viewing Angles.
ALL DIMENSIONS ARE IN MILLIMETRES
15
35
25
Mounting Slot
18 X 5.2
SIDE VIEW TOP VIEW
90 DEGREES